Hinet UPS User Manual
The List of possible Alarm and the associate help messages is displayed below.
ALARM MESSAGE
INVERTER OFF
INVERTER OVERLOAD
BYPASS SWITCH LOCKED
BATTERY FAILURE
INVERTER SHUT-DOWN
IMMINENT
BYPASS SWITCH FAILURE
MANUAL BYPASS ON
MAIN OUT OF LIMITS
BYPASS LINE OUT OF
LIMITS
EMERGENCY POWER OFF
BATTERY NOT CONNECTED
BATTERY CHARGER FAULT
HIGH BATTERY VOLTAGE
LEVEL
END OF BATTERY DISCHARGE
4.2.3

COMMAND MODE MENU

In this menu is possible to give some operative command to the UPS.
MESSAGE
BATTERY TEST
SWITCH LOAD
INVERTER ON/OFF
CAUSE
Initial Start Up
Permanent Overload has been
detected
Continuos Overload on UPS Output
High Transient Loads on UPS
Output. Inrush Load Current
After 3 times
Battery Test not OK
Battery almost flat, next to
Shut-Down of inverter
One or more Phases in the Output
are missing
UPS on Maintenance
Breaker is Open
Main Input is missing
The input phase rotation is not
correct
Input Voltage Missing
The Command EPO has been
selected
Battery Switch Open
Battery Test Failed
Battery Charger in Fault
Main is missing for long time
With this message displayed by pressing ENTER an automatic test on the Battery
will be performed instantaneously
With this message displayed by pressing ENTER the load is switched from inverter
to the Bypass Line. This command is also used for reset the alarm conditions on the
bypass line. For instance when the Alarm Bypass Switch Locked is present because
for three consecutive times the load has been connected to Bypass for transient
overload. To reconnect the load on inverter is necessary to activate this command by
ENTER
With this message displayed by pressing ENTER the User can Turn-on or Turn-off
the Inverter in a permanent way and connect it to the Load.
It is necessary Turn-on the Inverter at the start-up and after a permanent overload.
(12/01)
ACTION
Start the Inverter
Check Output
Check Output Load and Restart
Inverter
Check for Output Short-Circuit
Check Output Load and Restart
Inverter
Check Battery
Check Battery fuses
Make shut-down to the connected
Loads
Check SCR of Bypass
Check Bypass external connections
Check Main line Voltage and
Breaker position
Check Bypass line Voltage
Check Phase Rotation
Restart the UPS
Fully switch-off the Breakers and
the Battery Fuse, wait till the LCD
is complete switch-off then restart
the UPS
Call Service Office, to replace the
Battery Charger
Call Service Office, to replace the
Battery Charger
INTERPRETATION