Safety Relay - Siemens SIRIUS 3TK2822 Operating Instructions Manual

Safety relay

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 2
SIRIUS

Safety Relay

Operating Instructions
Read and understand these instructions before installing, operating, or maintai-
ning the equipment.
!
DANGER
Hazardous voltage.
Will cause death or serious injury.
Disconnect power before working on
equipment
The relay must be installed in switchgear cubicles complying with degree
of protection IP32, IP43 or IP54, depending on the prevailing environmental
conditions.
IMPORTANT NOTICE
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effecti-
veness of the safety system by trained individuals. Siemens AG, its subsidiaries
and affiliates (collectively "Siemens") are not in a position to evaluate all of the
characteristics of a given system or product or machine not designed by
SIEMENS.
Siemens accepts no liability for any recommendation that may be implied or
stated herein. The warranty contained in the contract of sale by Siemens is the
sole warranty of Siemens. Any statements contained herein do not create new
warranties or modify existing ones.
Application
You can use the safety relay 3TK2822 in safety circuits as per VDE 0113 Part 1
(11.98) or EN 60 204-1 (11.98), e.g. with movable covers and guard doors; the
safety relay 3TK2823 in EMERGENCY STOP devices as per EN 418. Depending on
external connections, category 4 as per DIN EN 954-1 is achievable.
Functions and connections
The safety relays 3TK2822/23 have two release circuits (safety circuits) configu-
red as NO circuits. The number of release circuits can be increased by adding
one or more 3TK2830 extension modules. Three LEDs indicate operating state
and function.
When the EMERGENCY STOP button or the limit switch is unlocked and when
the ON button is pressed, the internal circuit of the safety relay and the external
contactors are checked for proper functioning.
On the 3TK2823, the ON circuit Y33, Y34 is checked for short-circuit. This means
that a fault is detected when Y33, Y34 is closed before the EMERGENCY STOP
button is closed.
Connect the EMERGENCY STOP button or the limit switch to terminals Y11, Y12,
Y21, Y22. Connect the ON button in series with the NC contacts of the external
contactors (feedback circuit) to terminals Y33, Y34.
Terminal
Operating
A1
voltage
A2
assignments
Sensors
Y11, Y12
Y21, Y22
Y33, Y34
Outputs
13, 14
23, 24
2
Cable
for 2 x 1.5 mm
lengths
Figures
Fig. I:
Dimension drawings (dimensions in mm)
Fig. II: Installation/Cage Clamp
Fig. III: Internal circuit: ¿ PTC fuse
Fig. IV: 3TK2822 with Autostart for guard door monitoring,
category 4 per EN 954-1
Fig. V: 3TK2823 with monitored start for EMERGENCY STOP,
category 4 per EN 954-1
2
L/+
N/-
Channel 1 EMERGENCY STOP or limit switch
Channel 2 EMERGENCY STOP or limit switch
ON button, feedback circuit
Release circuit 1 (NO)
Release circuit 2 (NO)
max. 1000 m (total cable length for
sensors and power supply lines)
À Power pack
Á Control logic
 Channel 1
à Channel 2
Order No.: 3ZX1012-0TK28-2CA1
Operating states
LED
POWER
Channel 1 Channel 2 PS
Technical data
Permissible ambient temperature T
Operation/storage
Degree of protection to EN 60 529
Rated insulation voltage U
i
Rated impulse withstand voltage U
Rated control supply voltage U
s
Rated power
DC operating range
AC operating range
Shock resistance (half-sine) as per IEC 60068
Weight
Recovery time after EMERGENCY STOP 3TK2822
Release time after EMERGENCY STOP
Response time
Utilization
Rated operational
category
voltage U
e
as per DIN VDE 0660
(V)
Part 200, IEC 60947-5-1
AC-15
230
DC-13
24
115
230
Continuous current I
th
Short-circuit
Fuse links
protection for
Duty class
release circuit
The safety relay is protected by an internal self-healing PTC
fuse (multifuse).
Be sure to fit the specified fuses. Otherwise safe interruption
in the event of a fault cannot be guaranteed.
For further data and accessories see Catalog.
Reliable functioning of the equipment is only ensured with certified compon-
ents.
3TK2822, 3TK2823
DIN EN 60 947-5-1 (08.00)
English
Operation
EMERGENCY
ON
STOP
ON
not activated activated
activated
not activated open
not activated not activated open
Faults
• Relay fusion-welded
• Motor contactor fusion-welded
• Defect in electronics
• Short-circuit in ON circuit
(only with 3TK2823)
Cross or ground faults in
EMERGENCY STOP circuit (min. fault
current I
= 0.5 A; PTC fuse trips)
Kmin
u
25 to +60 °C/
40 to +80 °C
IP40, IP20 at terminals
300 V
4 kV
imp
24 V AC/DC
1.5 W
0.85 to 1.2 x U
s
0.85 to 1.1 x U
s
8 g/10 ms
0.240 kg
minimum 200 ms
3TK2823
minimum 400 ms
max. 20 ms
3TK2822
max. 80 ms
3TK2823
max. 30 ms
Rated operational current I
with all release circuits loaded
(A)
50 °C
60 °C
5
4.5
5
4.5
0.2
0.2
0.1
0.1
5
4.5
DIAZED
gL(gG)
6 A
quick response
10 A
Release
circuits
closed
open
e
70 °C
4
4
0.2
0.1
4

Advertisement

loading

This manual is also suitable for:

Sirius 3tk2823