AVIOTEC IP starlight 8000
8.2
Masking
Customized areas can be defined in the picture of the camera. These individual masks for
flame and smoke detection deactivation allow individual adoption to the application of the
customer.
8.2.1
Mask
Masks in which the detection will be deactivated can easily be added to the picture area.
To add a mask, perform the following steps:
1.
2.
3.
8.2.2
Time region mask
Detection disturbing elements in the application of the customer, e.g. roller shutter, can be
masked out. In a smoke time region mask, the smoke detection will be delayed.
To add a smoke time region mask, perform the following steps:
1.
2.
3.
4.
Bosch Sicherheitssysteme GmbH
Click on the button Add mask.
A rectangle with a crossed out flame and smoke icon will appear in the middle of the
picture area.
In Properties you can deselect Flame or Smoke.
Change the size and shape of the rectangle to your specific needs.
Move the mask to the desired area in the picture.
Click on the button Add smoke time region.
A rectangle with a clock icon will appear in the middle of the picture area.
In Properties select or type in the Verification time [sec].
The value must be set from 5 to 30 seconds. Default value is 30 seconds.
Move the mask to the desired area in the picture.
Change shape and size to your specific needs.
Operation Manual
Detection settings | en
37
2016.02 | 1.0 | F.01U.318.200