Omron CS1W-FLN22 Operation Manual page 263

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

FL-net Unit Support Software Ver. 1.6
(6) Receive
Reads the contents of the Unit Area Setup Area of the specified Unit to the FL-net Unit Support Software.
(7) OK
Validates the changed settings and closes the window.
When the Unit Area Setup Window is next opened, the changed settings will be displayed.
(8) Cancel
Cancels the changes to the settings and closes the window.
When the Unit Area Setup Window is next opened, the settings prior to the changes will be displayed.
Monitoring Function
The FL-net Unit Support Software can be used to monitor conditions such as the network status, settings, etc.
Several types of status can be displayed simultaneously, providing an accurate picture of network status.
Selecting the Monitoring Function
Select the data to be monitored, and then click the Start Button.
Note The monitoring function periodically reads data from the FL-net Unit or the PLC, so they may have an
effect on data link operations and message communications.
Use the monitoring function only when required. In particular, be careful about simultaneously displaying
several types of status, because this can have an especially noticeable effect on operations.
While executing the monitoring function, do not disconnect the communications cable between the com-
puter and the PLC, or turn OFF the power to the computer or the PLC.