Omron CS1W-FLN22 Operation Manual page 169

100base-tx, sysmac cs / cj series, fl-net units
Table of Contents

Advertisement

Internode Test
9-3-2
Checking Results
Test Status
Error Code
Error Flags
Number of Test Runs and Errors
Note
The results of the internode test are stored in the fourth through ninth words of
the portion of the CPU Bus Unit Area allocated to the FL-net Unit. The status
information area stores the test status and numbers of test runs and errors.
The result of the test run and descriptions of errors are stored as the test sta-
tus. The test status is stored at the word whose address is calculated by the
following formula:
Stored words = 1,500 + (25 × unit number) + 3
Bit
15
14
13
12
11
+3
Error code
If the test is run repeatedly, the code for the latest test results is stored.
Bit
15
14
13
0
0
0
1
1
1
The bits corresponding to errors are turned ON if errors occur. The flag status
is maintained until the internode test is run again.
The number of test runs and total errors from the time the test is started until it
is stopped is stored. The configuration of this area is shown in the following
table. Each result is stored at a word relative to the first word the address of
which can be calculated using the following formula:
Stored words = 1500 + (25 × unit number) + 3 to +5
Bit 15
14
13
12
11
+3 ---
+4 Number of timeout errors
+5 Number of send errors
1. The contents of the test status area and test runs/errors area are main-
tained until the internode test is run again.
2. When the number of tests counts to the maximum value (FF Hex), subse-
quent internode test runs are counted from 0. However, the maximum val-
ue is maintained and further errors are not counted when the number of
errors reaches the maximum value.
10
9
8
7
6
5
1: Timeout error
1: Response error
1: Send error
1: Data not matched error
1: Send parameter error
Description
Normal
Insufficient memory error
10 9 8
7
6 5
No. of test runs
No. of response errors
No. of times the data did not match
Section 9-3
4
3
2
1
0
4
3
2 1
0
143