Product Information / Produktinformation A6620
Analog I/O Card
Current output − characteristical value
The calculation of the characteristical value and its evaluation depends on the function
determined during configuration.
Current output 1
Current output 2
Current output 3
Current output 4
Nominal range
Life zero − mode
Accuracy / resolution
Permissible load

1.6.2 Visualization

4 green channel clear LEDs on the front panel, one for each channel
Channel status = no error (OK)
Channel status = error
8 yellow LEDs for advising limit exceedings.
limit exceedings
no limit exceedings
Channel Clear outputs
Opto−decoupled collector/emitter segments
Channel clear channel 1
Channel clear channel 2
Channel clear channel 3
Channel clear channel 4
Voltage supply
GND for all outputs
Ext. disabled or status = failure
Not ext. disabled and status = OK
I1+: z16 / I1−: z18 (galvanically isolated)
I2+: d20 / I2−: d22 (galvanically isolated)
I3+: b20 / I3−: b22 (galvanically isolated)
I4+: z20 / I4−: z22 (galvanically isolated)
0...20 mA or 4...20 mA, depending on configuration
in the 4...20 mA mode the output con be set to 0 mA
in case of a fault. This function is activated during
configuration.
±1 % of f.s.d. / 16 bit
500 Ω
Continuous light
Dark
Continuous light
Dark
d26
b26
z26
d28
d24 and z24 (redundant)
b24
C−E non conducting, max perm. voltage 45 V
C−E conducting, max. perm. current: 200 mA
Page 13