Download Print this page

Carrier 58MSA040-08 Installation, Start-Up, And Operating Instructions Manual page 35

4-way multipoise fixed-capacity condensing gas furnace

Advertisement

and &y. Assemble
theelastomeric
(rllbber) ventcoupling
(with 2loose c lamps) onto inducer housing connection.
Insert
the 2-in. d iameter
vent p ipe through theelastomeric
(rllbber)
coupling and _hlly intoinducer housing connection
untilit
bottoms onthe internal stop.
Tighten
both clamps to secure the
pipe to inducer
housing.
Tighten
the clamp screws
to 15 inMb.
of torque.
5. Install
casing
hole
filler
cap (fhctolT-supplied
in loose parts
bag) in unused
vent pipe casing hole.
VENT
EXTENSION
PIPE
Some filrnaces
are supplied
with
a PVC vent extension
pipe
(2-in.
diameter
by
12=in.
tong).
This
pipe
has
a built-in
channel
to assist
vent
condensate
disposal.
When
this vent
extension
pipe is supplied,
it must be used to connect
the field
vent
pipe
to filrnace
inducer
housing
on ALL
upflow
and
downflow
applications.
NOTE:
See label on vent extension
pipe for proper
installation
This pipe may be shortened
if an elbow
is used to connect
vent
extension
robe to field-installed
vent pipe.
5. Working
fiom
fi/rnace
to
outside,
cut
pipe
to
required
length(s).
7. Deburr
inside and outside
of pipe.
8. Chamfer
outside
edge of pipe for better distribution
of primer
and cement.
9. Clean and d_
all surfitces
to be joined.
10. Check &y fit of pipe and mark
insertion
depth
on pipe.
NOTE:
It is recommended
that
all pipes
be cut, prepared,
and
preassembled
before
pem?anently
cementing
any joint.
11. After pipes have been
cut and preassembled,
apply
generous
layer of cement
primer
to pipe fitting
socket
and end of pipe
to insertion
mark.
Quickly
apply
approved
cement
to end of
pipe and fitdng socket Cover primer).
Apply
cement
in a light,
uni[bm_
coat on inside of socket to prevent
buildup
of excess
cement.
Apply
second
coat.
12. While
cement
is still wet, twist pipe into socket with 1/4 turn.
Be sure pipe is [:ully inserted
into fitting
socket.
13. Wipe excess
cement
fiom joint.
A continuous
bead of cement
will be visible
around
perimeter
of a properly
made joint.
14. Handle
pipe joints
carefidly
until cement
sets.
15. Support
vent piping a minimum
of every 5 ft (3 ft for SDR=2!
or -26 PVC) using perforated
metal
hanging
shap.
16. Slope vent pipe downward
toward
Nrnace
a minimum
of 1/4
in. per linear
ft with no sags between
hangers.
17. Use appropriate
methods
to seal openings
where
vent pipe
passes
through
roof or sidewall.
Extended
Exposed
Sidewall
Pipes
Sidewall
vent
pipe
tem?ination
may
be extended
beyond
area
shown in Fig. 40 in outside
ambient
by insulating
pipe as indicated
in Table 9.
1. Detemline
vent pipe diameter,
as stated above, using total pipe
length
and number
of elbows.
2. Find appropriate
temperature
fPr your application
and furnace
model
using
winter
design
temperature
(used in load calcula=
tions).
3. Detem_ine
required
insulation
thickness
fbr
exposed
pipe
lengths.
NOTE:
Pipe
length
(ft)
specified
l\)r maximum
pipe
lengths
located
in unconditioned
spaces
cannot exceed
total allowable
pipe
length
as specified
in Table
8.
35
VENT
TERMINATION
Vent
pipe must
terminate
either
through
roof or sidewall.
See
Table
10 _br required
clearances.
See Fig
39, 40, and
41 _br
exterior
piping
an'angements
Consideration
of the _Pllowing
should
be made when determining
an appropriate
location
for tem_ination:
1. (omply
with all clearance
requirements
stated
in Table
10.
2. Termination
should
be positioned
where
vent vapors
will not
damage
plants/shrubs
or air conditioning
equipment.
3. Tem_ination
should
be positioned
where
it will not be dan>
aged by or subjected
to foreign
objects
such as stones,
balls,
etc.
4. Termination
should be positioned
where
vent vapors
are not
objectionable.
MULTIVENTING
When 2 or more 58MSA
Furnaces
are vented near each other, each
fitmace
must
be individually
vented
NEVER
common
vent
or
breach
vent 58MSA
fiu_aces
Step
lO--Condensate
Drain
GENERAL
Condensate
trap is shipped
installed
in the blower
shelf and [itctory
connected
_br UPFLOW
applications.
Condensate
trap must
be
RELOCATED
_br use
in
DOVv_TLOW
and
HORIZONTAL
applications.
(ondensate
trap MUST
be used for all applications.
An external
trap is not required
when
connecting
the field drain to
this condensate
trap.
The field drain connection
(condensate
flap or drain robe coupling)
is sized
fPr
1i2=im
CPV(,
1/2-in.
PVC,
or 5/8=in.
ID
robe
connection.
Drain
pipe
and fitdngs
must
conform
to ANSI
standards
and
ASTM
D1785,
D2466
or D2846.
CPVC
or PV(
cement
must
conform
to ASTM
D2564
or F493. Primer
must conform
to ASTM
F656.
In Canada,
use CSA or ULC
listed schedule
40 CPV(
or
PVC drain
pipe, fittings,
and cement.
When
a condensate
pump
is required,
select
a pump
which
is
approved
tbr condensing
furnace
applications.
To avoid
conden-
sate spillage,
select
a pump
with an overflow
switch.
UNIT
MAY
NOT
OPERATE
Failure
to _bllow this caution
may result
in intem_ittent
unit
operation.
Unit must not be installed,
operated,
and then mined
off and
left in an unconditioned
structure
doting
cold weather
when
temperature
&ops
to 32°F and below
unless
drain
trap and
&ain
line have adequate
[i'eeze protection.
See Service
and
Maintenance
Instructions
_Br winterizing
procedures.
(See
Fig. 15.)
Furnace
condensate
is mildly
acidic,
typically
in the pH range
of
32 to 4.5 Due to cotl'osive
nature
of unneutralized
condensate,
a
condensate
pH neutralizing
filter may be desired.
Check with local
authorities
to determine
if a pH neutralizer
is required
APPLICATION
The f_lrnace, A/C,
and humidifier
drains
may be combined
and
drained
together.
The Ai(
drain
retest have
an external,
field-
supplied
trap
prior
to the
fi/rnace
drain
connection.
Al! drain
connections
(furnace,
A/C, or humidifier)
must be tem_inated
into

Advertisement

loading