Carrier 58MSA Service And Maintenance Instructions
Carrier 58MSA Service And Maintenance Instructions

Carrier 58MSA Service And Maintenance Instructions

4-way multipoise fixed-capacity condensing gas furnace

Advertisement

Visit www.carrier.com
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before performing any
service or maintenance.
This symbol
indicates a change since the last issue.
Index
SAFETY CONSIDERATIONS..................................................1-2
GENERAL......................................................................................2
CARE AND MAINTENANCE................................................2-10
Cleaning and/or Replacing Air Filter.......................................3
Blower Motor and Wheel Maintenance................................3-4
Cleaning Burners ...................................................................4-5
Cleaning Heat Exchangers ....................................................5-6
Primary Heat Exchangers ................................................5-6
Secondary Heat Exchangers................................................6
Servicing Hot Surface Ignitor ...............................................7-8
Electrical Controls and Wiring.................................................8
Troubleshooting ...................................................................8-10
Winterizing..............................................................................10
WIRING DIAGRAM...................................................................12
SERVICE LABEL .......................................................................13
TROUBLESHOOTING GUIDE ............................................14-15

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified person-
nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA
54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 535-744
Tab 6a 8a
For Sizes 040-120, Series 110
A93040
Page
Printed in U.S.A.
4-Way Multipoise Fixed-Capacity
Condensing Gas Furnace
®
ama
A PP R O VED
R
As an ENERGY STAR®
Partner, Carrier Corporation
has determined that this prod-
uct
meets
the
ENERGY
STAR® guidelines for energy
efficiency.
REGISTERED QUALITY SYSTEM
Fig. 1-Multipoise Furnace in Upflow Orienta-
Air Heating and Air Conditioning Systems (NFPA 90B)
ANSI/NFPA 90B. In Canada, refer to the CAN/CGA-B149.1- and
.2-M95 National Standard of Canada, Natural Gas and Propane
Installation Codes (NSCNGPIC). Wear safety glasses and work
gloves. Have a fire extinguisher available during start-up and
adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Form 58MSA-3SM
Pg 1
58MSA
A98306
tion
5-99
Replaces: 58MSA-2SM
.

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 58MSA

  • Page 1: Table Of Contents

    4-Way Multipoise Fixed-Capacity Condensing Gas Furnace ® A93040 A PP R O VED Page As an ENERGY STAR® Partner, Carrier Corporation has determined that this prod- meets ENERGY STAR® guidelines for energy efficiency. REGISTERED QUALITY SYSTEM Fig. 1—Multipoise Furnace in Upflow Orienta- Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B.
  • Page 2: Electrostatic Discharge (Esd) Precautions

    Therefore, since this furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location accordingly.
  • Page 3: Cleaning And/Or Replacing Air Filter

    4. Position control box, transformer, and door switch assembly to right side of furnace casing. 5. If condensate trap is located in left- or right-hand side of furnace casing, proceed to item 6, otherwise remove trap and tubing as described below. a. Disconnect field drain connection from condensate trap.
  • Page 4: Cleaning Burners

    12. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices. 13. Reconnect wires to gas valve. Refer to furnace wiring diagram for proper wire location. 14. Reinstall burner box pressure tube to gas valve regulator fitting.
  • Page 5: Cleaning Heat Exchangers

    (See Fig. 7.) Fig. 7—Combustion-Air Intake Housing Gasket Repair 13. Refer to furnace wiring diagram and connect wires to rollout switch, gas valve, ignitor, and flame sensor. 14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door for proper tube location.
  • Page 6: Burner Flame

    Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below. Tube location when used in UPFLOW application Condensate Trap; Factory Installed in Blower Shelf (Blower access panel removed) COLLECTOR BOX TUBE...
  • Page 7: Servicing Hot Surface Ignitor

    6702, or Dow-Corning RTV 738 sealant to groove in collector box. Fig. 10—Gasket on Collector Box 11. Refer to furnace wiring diagram and connect wires to inducer motor and pressure switch or connectors. 12. Reconnect pressure tubes to pressure switch. See diagram on main furnace door for proper location of tubes.
  • Page 8: Electrical Controls And Wiring

    Step 8—Troubleshooting For an explanation of fault codes, refer to service label located on back of main furnace door or Fig. 16, and the Troubleshooting Guide. The control center stores 1 fault code (the last fault to occur) for a period of 48 hrs or until the 115- or 24-v power is interrupted.
  • Page 9: Checking Heat Tape Operation (If Applicable)

    6. After component test is completed and LED is ON continu- ously indicating the furnace is ready to operate when a signal from the thermostat is received, replace main furnace door. INITIATING COMPONENT TEST AND RETRIEVING STA- TUS CODE BY JUMPERING CONTROL TEST TERMINAL 1.
  • Page 10: Winterizing

    Step 10—Winterizing Freezing condensate left in the furnace will damage the equipment. If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F or below, winterize as follows: 1. Turn off electrical supply to furnace.
  • Page 11 A99118 A99119 Fig. 13—Inducer Housing Drain Tube Fig. 14—Funnel in Drain and Antifreeze Running Through Trap...
  • Page 12: Wiring Diagram

    INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED SELECTION. 4. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SWITCH AND THE FURNACE JUNCTION BOX (JB). 5. THIS WIRE MUST BE CONNECTED TO FURNACE SHEETMETAL FOR CONTROL TO PROVE FLAME. 6. FACTORY CONNECTED WHEN LGPS NOT USED.
  • Page 13: Service Label

    - Defective Hot Surface Ignitor - Manual valve shut-off. - Low inlet gas pressure. - Green wire MUST be connected to furnace sheet metal. - Inadequate flame carryover or rough ignition. COMPONENT TEST To initiate the component test sequence,shut OFF the room thermostat or disconnect the "R"...