CHAPTER 3 COMMUNICATIONS DATA
3--10
The following shows the status contents.
Bit position
Bit position
0
Heater overcurrent
1
Heater current hold
2
HB (HBA) error
3
Spare
4
Spare
5
Display range exceeded
6
Input error
7
Spare
8
Control output 1
9
Control output 2
10
HB (HBA) output
11
Spare
12
Alarm output 1
13
Alarm output 2
14
Alarm output 3
15
Spare
16
Spare
17
Spare
18
Spare
19
Spare
20
Write mode
21
EEPROM
22
Setup area
23
AT execute/cancel
24
Run/Stop
25
Communications writing
26
Spare
27
Spare
28
Spare
29
Spare
30
Spare
31
Spare
*1 "1" is set and the heater current is held at the immediately previous current value when
the control output ON time is less than 190 ms.
*2 Whenever the control output is the current output, this is OFF.
*
"Spare" bits are always OFF.
Status
Status
Not generated
*1
Updated
Not generated
Not generated
Not generated
*2
OFF
OFF
OFF
OFF
OFF
*3
OFF
Backup mode
RAM=EEPROM
Setup area 0
AT canceled
Run
OFF (disabled)
Bit Description
0
1
Generated
Hold
Generated
Generated
Generated
ON
ON
ON
ON
ON
ON
RAM write mode
RAM¸EEPROM
Setup area 1
AT execution in
progress
Stop
ON (enabled)