Omron E5AN User Manual page 14

Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

CHAPTER 1 ABOUT COMMUNICATIONS METHODS
F Communications
parameter setup
1--6
Note that communications parameters are enabled after they have been
changed by resetting the controller.
· Communications unit No. (
This parameter is for setting the unit No. to each of the temperature con-
trollers. This unit No. is set so that the host computer can identify the
temperature controller when communications are carried out with the
host computer. Set a unit No. within the range 0 to 99 for each tempera-
ture controller connected to the host computer on the network. Default
is "1". When two or more temperature controllers are used, do not set
the same unit No. Doing so will prevent normal operation.
· Baud rate (
)
This parameter is for setting the baud rate when communicating with
the host computer. Set one of "1.2 (1200 bps)", "2.4 (2400 bps)", "4.8
(4800 bps)", "9.6 (9600 bps)" and "19.2 (19200 bps)".
· Communications data length (
This parameter is for setting the communications data length. Set either
of "7 bits" or "8 bits".
· Communications stop bit (
This parameter is for setting the communications stop bit. Set either of
"1" or "2".
· Communications parity (
This parameter is for setting the communications parity. Set one of
"none", "even" or "odd".
)
)
)
)