MICROVIP3 PLUS SET UP PAGES
PAG
SEt-UP
MEAS
PAG
SEL
SEL
12 pages of three-phase measurements
7 pages of single-phase measurements
PAG
PAG
V
A
000100
000005
P.t. 100
C.t. 1.00
Use SEL and SET
to select PT primary
(from 1 to 999999 V)
and PT secondary
(57.7,63.5,100,110,115,
120,173,190,200,220 V),
CT primary (from 1 to
999999 A) and CT
secondary (from 0.01
to 1.00 V).
SET
PAG
* Note 1: these 3 pages are present only when LOG off.
PAG
PAG
Std1
StAr
n
inSErt
OPtio
SET
SET
Std2
dELtA
OPtion
inSErt
SET
SET
2 PH
inSErt
COG4
SET
OPtion
Std1: kWh,kvarh
Std2: kWh,kVAh
COG: ± kWh, ± kvarh
PAG
PAG
PAG
m
Int 15
thd
50 Hz
tiME
SET
Use SET
to select
thd
1,2,5,10
60Hz
15,20,30,
60 minutes. SET
thd
OFF
SET
SET
thd
Fnd 50 Hz
SET
thd
Fnd 60 Hz
Fundamental frequency
selection: 50 Hz or 60 Hz;
OFF = no harmonic
measurements and printouts.
Fnd = thd referred to the fundamental
instead of rms value.
II
SHORT FORM
PAG
PAG
*
*
m
Std
LOG 01
LOG
rAtE
SET
Use SEL
and SET
to select
from 1 to
99 minutes
of data
recording
rate.
00 = 3"
SAMPLE
LOG
Std LOG = rms values
Sample LOG = V,I waveforms samples
Changing LOG type and confirming
by PAG., makes the display blinking
for 5" -10".
Use SEL and
SET to select
baud rate
,
(1200
,
2400,4800,9600
),
19200,38400
data bits (7/8),
stop bits (1/2),
parity (no/e/o).
k
COM 9.60
n 7 1
PAG
*
LOG no
CLEAr
SET
LOG YES
CLEAr
Press PAG
to clear
internal
memory;
display blinks
for 5"-10"
.