McQuay OM 920-1
Six Equal Sized Compressors, Six Circuits, No WRV
Only one sequence is provided so the user makes no selections.
• Total cooling stages = 6.
• Maximum cooling stages is always set to 6.
• The Staging sequence is the Standard sequence that contains the enabled Stage 1
Compressor with the fewest run hours. Compressors in disabled circuits are ignored when
only enabled compressor run hours are compared.
• The Compressor Sequence changes only when the compressor stage is Maximum cooling
stages or zero. This means that disabling and re-enabling the compressors or turning the unit
off and on may be necessary to cause sequence changes.
• The same staging sequence is used whether a circuit is disabled or not. This means that units
will remain at a stage for an extra stage time when staging up if a disabled circuit is added at
that stage. It also means that units will remain at a stage for an extra stage times when
staging down if a disabled circuit is turned off at that stage.
• Any compressor on the disabled circuit stays off if it is already off and is turned off if it's on.
Table 65: Standard Staging
Staging
Stage 1
Sequence
Comps
Std-1
1
Std-2
2
Std-3
3
Std-4
4
Std-5
5
Std-6
6
StgdClgCap
17%
Six Equal Sized Compressors, Six Circuits, Water Regulating Valve
Only one sequence is provided so the user makes no selections.
• Total cooling stages = 6.
• Maximum cooling stages is always set to 6.
• If both circuit # 1 and circuit # 2 are enabled, the staging sequence is Std-1 if compressor # 1
has fewer hours than compressor # 2, and the staging sequence is Std-2 if compressor # 1
does not have fewer hours than compressor # 2.
• If Circuit # 1 is disabled, the staging sequence is Std-2.
• If Circuit # 2 is disabled, the staging sequence is Std-1.
• If both circuit # 1 and circuit # 2 are disabled, the staging sequence is Std-1. Only
compressors 3, 4, 5, and 6 are used.
• The Compressor Sequence changes based on Run Time only when the compressor stage
equals Maximum cooling stages or zero. This means that disabling and re-enabling the
compressors or turning the unit off and on may be necessary to cause sequence changes.
• The compressor sequence changes immediately if a circuit is disabled to keep either
compressor # 1 or # 2 on. This will result is compressors being turned off and others being
turned on in this emergency condition.
• The same staging sequence is used whether a circuit is disabled or not. This means that units
will remain at a stage for an extra stage time when staging up if a disabled circuit is added at
that stage. It also means that units will remain at a stage for an extra stage times when
staging down if a disabled circuit is turned off at that stage.
Standard Staging
Stage 2
Stage 3
Stage 4
Comps
Comps
Comps
1,2
1,2,3
1,2,3,4
2,3
2,3,4
2,3,4,5
3,4
3,4,5
3,4,5,6
4,5
4,5,6
1,4,5,6
5,6
1,5,6
1,2,5,6
1,6
1,2,6
1,2,3,6
33%
50%
Operator's Guide
Stage 5
Stage 6
Comps
Comps
1,2,3,4,5
1,2,3,4,5,6
2,3,4,5,6
1,2,3,4,5,6
1,3,4,5,6
1,2,3,4,5,6
1,2,4,5,6
1,2,3,4,5,6
1,2,3,5,6
1,2,3,4,5,6
1,2,3,4,6
1,2,3,4,5,6
67%
83%
100%