Smart Managed Compact Switch
Switching to "Default"
mode
156
PHOENIX CONTACT
Figure 9-1
"Operating Mode" web page
When the switch is reset to "Default" mode from "PROFINET" mode, the following settings
are made:
–
LLDP remains active with the values set by default.
–
IP address assignment is set to BootP.
–
The station name for the switch does not change. If no station name has been specified,
the device type is entered.
It is recommended to save the new configuration after changing operating mode. Please
note that some configuration modifications only take effect after a restart.
9.2
Switch as a PROFINET device
9.2.1
Configuration in the engineering tool
9.2.1.1
Specifying the bus configuration
The switch can be operated as a PROFINET device if it is integrated under a controller in
the bus configuration in the engineering tool. A GSD file and an FDCML file for integration
can be downloaded at www.download.phoenixcontact.com.