Reference Conditions: 23°C ±5°C, 45 to 75% RH, 3V supply, conductor centered, earth's
magnetic field, no external magnetic or electrical field, sine wave 50/60Hz. Accuracy is
expressed as ± [% of reading (R) ± counts (cts)].
3.1
Electrical Specifications
AC Amperes
Range
Resolution
400A
0.1A
AC Volts (Auto-ranging)
Range Measurement
400V
0.5 to 399.9V
600V
400 to 600V
Resistance - Ohms (Ω)
Range
Measurement
400Ω
0.3 to 399.9Ω
Continuity (
Range
6
Shop for AEMC products online at:
CHAPTER 3

SPECIFICATIONS

Accuracy
50 to 60Hz: 2% of R ± 5cts
60 to 500Hz: 2.8% of R ± 5cts
Res.
0.1V
1.0% of R ± 5cts
60 to 500Hz:
1V
1.5% of R ± 5cts
Res.
0.1Ω
)
Beeper
< 35Ω
ShopAEMC
www.
Accuracy
Overload
50 to 60Hz:
600Vrms
Accuracy
Test Voltage Overload
1.9% of R
1.5V
± 3cts
Test Voltage
1.5V
DC
Clamp-on Meter Model 500
.com
Overload
600Arms
Input
Impedance
1MΩ
600Vrms
DC
Overload
600Vrms
1.888.610.7664