5. Setting up TROUBLE input delay time
If there are TROUBLE inputs, TROUBLE output and message operate after set delay
time. Range of delay time to be set is between 1 and 99 second(s).
— When
key (6) is pressed, the numeric keyboard appears. If you enter delay
time and hit ENT key, it is set up; if you enter ESC key, it is cancelled.

3.3 Display Screen for Setup of PID ZONE

There can be up to 6 ZONEs for the range of temperature PID constant
and they are controlled by the PID constants in the ZONE field in which set points (SP)
of temperature exist.
Initial setup at the time of product shipment is ZONE 1 fields and all fields are controlled
by a single PID constant.
Return to CONTROL SET screen
(2) Temperature ZONE
classifying constant T2
setup key
(1) Temperature ZONE
classifying constant T1
setup key
PID ZONE
EXIT
T1
1
2
T1
= -50
T4 = 100
(4) Temperature ZONE
(5) Temperature ZONE
classifying constant T4
classifying constant T5
setup key
setup key
<Figure 3.3.1>
- 15 -
T2
3
4
5
6
T3
T4
T5
T2 =
0
T3 = 50
T5 = 200
DISP
(3) Temperature ZONE
classifying constant T3
setup key
(6) ZONE range
redrawing key