Specifications; General Specifications - Honeywell IPC500 Installation Manual

Programmable
Table of Contents

Advertisement

4. SPECIFICATIONS

4.1 General Specifications

Item
Temperature input range
Indicator
Display screen
Number of dots
Display
device
Back light
Display size
Display color
Setup method
A/D conversion
Indication
temperature
Measure display
Input sampling cycle
Clock accuracy
Backup
Initial set value
Power voltage
Power frequency
Isolation resistance
Withstand voltage
Ambient temperature
Exterior
Mounting
Exterior size
Panel cut
-100.0~300.0°C
Dot matrix LCD module
86.37(H)X115.17(W)mm
240(H)X320(W) dot
CCFL cathode type fluorescent lamp (Brightness : 100 cd/m
40 lines X 30 lines ( case of 8X8 dot characters)
Blue characters on a white ground
Touch key method
Dual integral method
15bit (0.01 resolution with 300°C span)
± 0.1%FS ± 1digit
0.01°C / 0.1°C display switch available
0.5 second
± 10 PPM(25°C standard), temperature specificity -10~70°C:+10/-120 PPM)
Program data, control stated number : nickel manganese secondary battery
Data is preserved for 5 years after break-off of power supply (provided that
Full Charge is preceded)
EEPROM storage, more than ten years
AC 85 ~ 264 V
50/60Hz
50MΩ min. between case and terminals using a 500V DC Mega
AC1500V, 1 min, between case and power terminals
0 ~ 50°C
Case: steel painting (ivory), front panel : plastic
Panel-mount
210mm(H)X130mm(W)X188mm(D)
199.5mm(H)X119mm(W)