YASKAWA Z1000 User Manual page 223

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Digital Operator Display
Cause
Surge voltage present in the drive input
power.
The motor is short-circuited.
Ground current has overcharged the main
circuit capacitors via the drive input power.
Noise interference causes the drive to
operate incorrectly.
Digital Operator Display
PASS
Cause
MEMOBUS/Modbus test has finished
normally.
Digital Operator Display
Cause
A digital input set to 67H (MEMOBUS/
Modbus test) was closed while the drive
was running.
Digital Operator Display
TrPC
Cause
IGBTs have reached 90% of their expected
performance life.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
DC Bus Overvoltage
ov
The DC bus voltage exceeded the trip point.
For 600 V class drives: approximately 1040 V
• Install a DC link choke or an AC reactor.
• Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same
drive input power system.
• Check the motor power cable, relay terminals and motor terminal box for short circuits.
• Correct grounding shorts and turn the power back on.
• Review possible solutions for handling noise interference.
• Review section on handling noise interference and check control circuit lines, main circuit lines and ground
wiring.
• If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil.
Set number of fault restarts (L5-01) to a value other than 0.
MEMOBUS/Modbus Comm. Test Mode Complete
This verifies that the test was successful.
MEMOBUS/Modbus Communication Test Mode Error
SE
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-oo = 10).
Stop the drive and run the test again.
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Replace the drive.
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
5.5 Alarm Detection
223