Caution on refrigerant leakage

This air conditioner uses R410A as refrigerant, which is
safe and noncombustible.
The room housing the air conditioner should be big
enough so that a refrigerant leakage cannot reach critical
thickness.
Critical thickness-----the max thickness of Freon without
harming people. R410A critical thickness: 0.42 [ kg/m
Outdoor unit
Indoor unit
Room full of leaking refrigerant
Calculate the critical thickness as follows and take the
necessary action.
Calculate the sum of the charge volume (A[kg])
Total
refrigerant
volume=refrigerant
delivered (nameplate)+super addition
Calculate the indoor cubage (B[m3]) (as the minimum
cubage)
Calculate the refrigerant thickness.
A [ kg]
≤ Critical thickness:0.42 [kg/m
B [ m
3
]
Countermeasure against excessive thickness
Install a mechanical ventilator to reduce the refrigerant
thickness to under the critical level (ventilate regularly).
Install a leakage detector alarm for the mechanical
ventilator if you cannot regularly ventilate the room.
b. A leakage detector alarm
for mechanical ventilator
Indoor unit
OA
(all refrigerant has leaked out)
Fig.7-2
volume
3
]
a: Ventilation opening
7.6

Hand over to the customer

Give the installation manual for the indoor unit and outdoor
unit to the user.