4.11 Mount the air deflector

(If the static pressure of outdoor unit is over 20 Pa, the
unit needs to be customized.)
8~12HP Installation illustration
Example A
750
Support
D
θ
Air outlet louver dimension (optional)
8 ST3.9 self-threading screws
750
340
Fig.4-20
Radius
E
C
A
Radius
731
B
Fig.4-21
Remove the
iron filter firstly
Fig.4-22
Fig.4-23
8×φ3.3
Unit: mm
Table.4-5
A
A≥300
B
B≥250
C
C≤3000
731≤D≤770
D
E
E=A+731
θ
≤15°
θ
Example B
Support
θ
Air outlet louver dimension (optional)
731
Fig.4-25
Static pressure
Remark
Factory default
0Pa
Remove the wire mesh and connect it to
0~20Pa
the wind duct (less than 3 meters).
Above 20Pa
Customization needed
C
D
Radius
750
A
Radius
B
Fig.4-24
8 ST3.9 self-threading screws
Remove the
iron filter first
Fig.4-26
A
A≥300
B
B≥250
C
C≤3000
D=A+750
D
θ
θ
≤15°
Table.4-4
Installation manual
9