Installation Illustration - Carrier Xpower Series Installation Manual

Full dc inverter xpower vrf outdoor unit
Hide thumbs Also See for Xpower Series:
Table of Contents

Advertisement

14~22HP Installation illustration
1290
Example A
Support
D
θ
12 x ST3.9 self-threading screws
300
1020
1290
A
A≥300
B
B≥250
C
C≤3000
630≤D≤660
D
E
E=A+630
θ
≤15°
θ
Static pressure
Remark
Factory default
0Pa
Remove the wire mesh and connect them
0~20Pa
to the wind duct (less than 3 meters).
Above 20Pa
Customization needed
Installation manual
10
Fig.4-27
E
C
Radius
A
Radius
630
B
Fig.4-28
Remove the two
iron filters first
Fig.4-29
12×φ3.3
Fig.4-30
Table.4-5
Example B
Support
θ
Air outlet louver dimension (optional)
630
Fig.4-32
Before installing the air deflector, remove the mesh enclosure to
prevent air supply blockages.
Mounting the shutter on the unit limits the air volume, cooling
(heating) capacity, and efficiency depending on the shutter
angle. Do not mount the shutter or keep it angled to under 15°.
Only one bending site is allowed in the air duct (see as above
figure) or the unit may not function normally.
Install the flexible connector between the unit and the air pipe
to avoid noise from vibrations
C
1290
A
Radius
B
Fig.4-31
12 x ST3.9 self-threading screws
Remove the
two iron filters first
Fig.4-33
A
A≥300
B
B≥250
C
C≤3000
D=A+1290
D
θ
≤15°
θ
NOTE
D
Radius