Page 1
Carrier T R A N S I C O L D REFRIGERATION CONNECTION CPR ADJUSTMENT & INTEGRA 35 X CHARGE TXV ADJUSTEMENT P/N : 62-61309-01 / rev B...
Page 2
Carrier T R A N S I C O L D ITEM 90° ORS 1/4->3/8" 40-60048-01 90° ORS 3/8" 40-60048-02 Liquid 135° ORS 3/8" 40-60049-02 Standby suction Road Suction ° ORS 3/8" Check valve 90° ORS 1/2" 40-60048-03 90° ORS 5/8"...
" HEAT DEFROST " mode Adjust the CPR to get the following gauge pressure values STANDARD ADJUSTMENT XARIOS 350 : 2,4 bars (35 psig) Pressure value is given at the CPR port CPR adjustment must be increased by : (bar)
Page 4
Road (2400 rpm) or Standby mode Superheat area Run the unit on " COOL " mode INITIAL CHARGE XARIOS 350 = 1,7 Kg Beginning of evaporating Evaporating of the last liquid drop COMPLETE THE CHARGE ON THE SIGHT GLASS AT 0°C BOX TEMPERATURE...