Hitachi P1-00044-L Basic Manual page 69

Sj series
Hide thumbs Also See for P1-00044-L:
Table of Contents

Advertisement

Chapter 4
[AG101]~[AG113]
Resonant frequency avoidance (Jump)
Code/Name
AG101
Jump frequency 1, 1st-motor
AG102
Jump frequency width 1,
1st-motor
AG103
Jump frequency 2, 1st-motor
AG104
Jump frequency width 2,
1st-motor
AG105
Jump frequency 3, 1st-motor
AG106
Jump frequency width 3,
1st-motor
・Prevents the passing of the output frequency in a
resonant point. Output frequency changes continuously.
Output
frequency
[AG105]
[AG103]
[AG101]
Motor Acc/Decel dwell (Hold)
Code/Name
AG110
Acceleration stop frequency
setting, 1st-motor
AG111
Acceleration stop time setting,
1st-motor
AG112
Deceleration stop frequency
setting, 1st-motor
AG113
Deceleration stop time setting,
1st-motor
・By using the dwell function when the inertial load is
considerable, if the set frequency is reached in the set
time the Acc/Decel of the frequency will be stopped.
・If the Intelligent input terminal function 100[HLD] is in
ON state, the acceleration and deceleration will be
stopped (Hold activation).
Output
Frequency
[AG112]
[AG110]
[AG111]
Initial
Range (unit)
value
0.00
590.00(Hz)
0.00
0.00
10.00(Hz)
0.00
0.00
590.00(Hz)
0.00
0.00
10.00(Hz)
0.00
0.00
590.00(Hz)
0.00
0.00
10.00(Hz)
0.00
[AG106]
[AG106]
[AG104]
[AG104]
[AG102]
[AG102]
Frequency
reference
Range (unit)
0.00
590.00(Hz) 0.00
0.00
60.00(s)
0.00
590.00(Hz) 0.00
0.00
60.00(s)
[AG113]
Time
For parameter configuration
Jogging function
Code/Name
AG-20
Jogging
frequency
AG-21
Jogging stop
selection
・When Input terminal [JG] is active (ON), if the operation
command is given the jogging frequency is outputted.
The frequency and stop method can be set when
performing jogging motion.
JG
FW
RV
Output
[AG-20]
Frequency
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Initial
Code/Name
value
AG201 Jump frequency 1, 2nd-motor
AG202 Jump frequency width 1, 2nd-motor
AG203 Jump frequency 2, 2nd-motor
0.00
AG204 Jump frequency width 2, 2nd-motor
AG205 Jump frequency 3, 2nd-motor
AG206 Jump frequency width 3, 2nd-motor
AG210 Acceleration stop frequency setting,
2nd-motor
0.00
AG211 Acceleration stop time setting 2nd-motor
AG212 Deceleration stop frequency setting,
2nd-motor
AG213 Deceleration stop time setting,,
2nd-motor
4-21
[AG-20]~[AG213]
Range (unit)
0.00~10.00(Hz)
00(free-running, disabled during operation)
01(decel/stop, disabled during operation)
02(DC braking, disabled during operation)
03(free-running, enabled during operation)
04(decel/stop, enabled during operation)
05(DC braking, enabled during operation)
Range
Initial
value
0.00
00
Initial
(unit)
value
Same as AG101
Same as AG102
Same as AG103
Same as AG104
Same as AG105
Same as AG106
Same as AG110
Same as AG111
Same as AG112
Same as AG113

Advertisement

Table of Contents
loading

Table of Contents