Chapter 7
7.3 Common specifications (continue)
Transistor output terminal 5, 1a contact relay 1 point, 1c contact relay 1 point
Intelligent output
RUN(While in run), FA1~5(Reached frequency signal), IRDY(Inverter ready), FWR(Forward rotation), RVR(Reverse rotation), FREF(panel
terminals
frequency reference), REF(panel motion operation), SETM(2nd-motor selected), OPO(Option-Output), AL(Alarm signal), MJA(Major
failure signal), OTQ(Over-torque), IP(Power loss), UV(Undervoltage), TRQ(Torque limited), IPS(Decel. Power loss), RNT(RUN time
exceeded), ONT(ON time exceeded), THM(Motor electronic thermal warning), THC(Electronic thermal warning), OH1(Motor temperature
increase), WAC(Capacitor life warning), WAF(Cooling-fan life warning), FR(Operation signal), OHF(heat sink overheat warning),
LOC/LOC2(Low-current indication signal), OL/OL2(Overload warning signal 1/2), BRK(Brake release)/BER(Brake error)/CON(Contactor
Relay/
control), ZS(0Hz detection signal), DSE(Maximum speed deviation), PDD(Maximum position deviation), POK(Positioning completed),
Alarm relay
PCMP(Pulse counter compare output), OD/OD2(Output deviation for PID control), FBV/FBV2(PID feedback comparison),
(1a, 1c) function
NDc(Communication disconnection), Ai1Dc/Ai2Dc/Ai3Dc(Analogue Ai1/Ai2/Ai3 disconnection), WCAi1/WCAi2/WCAi3(Window
comparator Ai1/Ai2/Ai3), LOG1~7(logical operation result 1~7), MO1~7(General-output 1~7), WFT(Trace waiting signal), TRA(Trace
running signal), LBK(Low battery of panel), OVS(Not assigned), the rest, is described in the contents of 4-35 "Output terminal function
list".
Functional safety diagnostic output
EDM output terminal
Output terminal monitor
The data of the monitor can be selected by the parameter of the output.
*6)
EMC filter can be enable (The filter exchange method can alter depending on the model)
EMC filter *7)
PC external access
USB Micro-B
ND
LD
Ambient temperature
VLD
-20~65°
Storage temperature *8)
20~90%RH(No condensation allowed)
Level of humidity
Model: up to P1-01240L(P1-220L)
Vibration tolerance *9)
Model: more than P1-01530L(P1-300L)
A maximum altitude of 1000m, without gases or dust.
Installation place *10)
The life span of the main circuit smoothing capacitors is 10 years.
Components life span
The life span of the cooling-fan is 10 years.
UL, cUL, CE marking, RCM, KC(Adquisition planned), EAC(Adquisition planned), NK(Adquisition planned),
Conformity standars *11)
Safety functions(STO:SIL3、Cat 3/PLe)(Adquisition planned)
Black
Coating color
3 ports
Optional slots
Analogue input/output option, relay output option
Input/ouput option
Ethernet(TCP/IP)、EtherCAT、PROFIBUS
Communication option
Line driver input(RS422), push-pull input, resolver
Feedback option
Temperature detector
Optional temperature measuring sensor
option
Functional safety option
Functional safety option
Braking resistor, AC reactor, noise filter,operator cable, harmonics suppresion unit, noise filter, LCRfilter, analog panel, regenerative
Other optional components
braking unit, power regeneration converter, sine wave converter, various control application devices, PC software ProdriveNext, relay
expansion terminal board, SJ300/SJ700 conection board
*6) The analogue voltage and analogue current monitor are estimated
outputs of the analogue meter connection. Maximum output value
might deviate slightly from 10V or 20mA by variation of the analogue
output circuit. If you want to change the characteristics, adjust the
Ao1 and Ao2 adjustment functions.
There is monitor data that cannot be part of the output.
*7) In order to enable the EMC filter, connect to the neutral grounding
supply. The leakage current may increase.
*8) Storage temperature is the temperature during transport.
*9) In accordance with the test methods of JIS C 60068-2-6:2010(IEC
60068-2-6:2007).
7.4 Current derating
For using with carrier frequency over 2.1 kHz, or when
changing load ratings to LD/VLD, refer to P1 user's guide
section "20.4 Current derating table".
-10~50°C
-10~45°C
-10~40°C
up toP1-00620H(P1-220H)
More than P1-00770H(P1-300H)
DP、PROFINET、BACnet/IP、DeviceNet
2
5.9m/s
(0.6G), 10~55Hz
2
2.94m/s
(0.3G), 10~55Hz
input、アブソリュートエンコーダ用
*10) In case of utilization at an altitude of 1000m or more, take into
account that the atmospheric pressure is reduced by 1% for every
100m up. Apply 1% derating from the rated current by increasing
every 100m, and conduct an evaluation test. Contact us when using
above 2500m ambient.
*11) Insulation distance is in accordance with the UL and CE standards.
7-4
Specifications