CHAPTER 6: ACTUAL VALUES
Base unit
POWER FACTOR
RTDs
SENSITIVE DIR POWER
(Sns Dir Power)
SOURCE CURRENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
STATOR DIFFERENTIAL CURRENT
(Stator Diff Iar, Ibr, and Icr)
STATOR RESTRAINING CURRENT
(Stator Diff Iad, Ibd, and Icd)
THERMAL MODEL
(Model Capacity Used)
(Model Motor Unbalance)
THERMAL MODEL
(Model Lockout Time)
THERMAL MODEL
(Thermal Model Load)
(Biased Motor Load)
THERMAL MODEL
(Trip Time on Overload)

6.3.9 RxGOOSE analogs

ACTUAL VALUES  METERING  RxGOOSE Analogs
 RxGOOSE
 Analogs
The M60 is provided with optional GOOSE communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.

6.3.10 Transducer inputs and outputs

6.3.10.1 RTD and DCmA inputs
ACTUAL VALUES  METERING  TRANSDUCER I/O DCMA INPUTS  DCMA INPUT xx
 DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Description
PF
= 1.00
BASE
BASE = 100°C
= maximum value of 3  V
P
BASE
BASE
for the sensitive power directional element(s).
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
BASE =100%
BASE = 10 minutes
BASE = 1.00 pu of FLA
BASE = 10 seconds
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
DCMA INPUT xx
0.000 mA
 I
for the +IN and –IN inputs of the sources configured
BASE
 I
for the +IN and –IN inputs
BASE
METERING
6
6-21