PRODUCT SETUP
Buffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows:
data-change
quality-change
integrity
general interrogation
Buffered Report1 IntgPd
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the period in milliseconds for generating Buffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.
Each unbuffered report has the following settings.
Unbuffered Report1 RptID
Range: 0 to 129 VisibleString characters
Default:
The entered value sets the RptID value in Unbuffered Report1 messages, and it can be used by the client to discriminate
Unbuffered Report1 messages from other messages. If the number of characters entered is zero, the value used for
5
RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/LLN0$RP$"URCB01".
Unbuffered Report1 DatSet
Range: None, DataSet01, DataSet02, ...
Default: None
This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Unbuffered
Report1 messages from other messages.
Unbuffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the confRev value in Unbuffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRef be incremented each time the members or the order of the members is changed, and each time the data
set name is changed.
Unbuffered Report1 OptFlds
Range: The check box for an individual bit can be enabled or not
Default: All bits true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The options are
as follows:
sequence-number
report-time-stamp
reason-for-inclusion
data-set-name
data-reference
5-60
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS