Dcma Outputs - GE M60 Instruction Manual

Motor protection system
Hide thumbs Also See for M60:
Table of Contents

Advertisement

TRANSDUCER INPUTS/OUTPUTS
RRTD 1 ALARM PKP DELAY
of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP TEMPERATURE
differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP PKP DELAY
to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP RST DELAY
RRTD 1 TRIP VOTING
element operates individually and no voting takes place.
A value of "Group" indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as well
(where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same group, there
needs to be at least one additional RTD of the same group picked up to issue a trip command.
The "Remote RTD 1" through "Remote RTD 12" values indicate that element is allowed to issue a trip if the corresponding
peer RTD is also picked up.
— This setting allows monitoring an open remote RTD sensor circuit. If this functionality is not required, then a
RRTD 1 OPEN
value of "None" disables monitoring and assertion of output operands. If set to "Alarm", the monitor sets an alarm when a
broken sensor is detected. If set to "Block", the monitor sets an alarm and simultaneously block remote RTD operation
when a broken sensor is detected.
If targets are enabled, a message appears on the display identifying the broken RTD. If this feature is used, it is
recommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action can
be taken.
— This setting is used to block remote RTD operation.
RRTD 1 BLOCK
5
SETTINGS
Function
Enabled = 1
Block
Off = 0
SETTING
ID
= RRTD 1
SETTING
Type
Temperature read
from RRTD
SETTING
Open
RUN
R > 1000 ohms
RUN

5.10.4 DCmA outputs

SETTINGS  TRANSDUCER I/O  DCMA OUTPUTS  DCMA OUTPUT H1(W8)
 DCMA OUTPUT H1
5-278
— This setting specifies time delay for the alarm stage until the output can be asserted. The range
— This setting specifies the temperature pickup level for the trip stage. The range of 1 to 200°C
— This setting specifies time delay for the trip stage until the output can be asserted. The range of 5
— This setting specifies the reset delay to seal-in the trip signal.
— This setting allows securing trip signal by voting with other RTDs. A value of "None" indicates that
Figure 5-157: Remote RTD input protection logic
AND
SETTINGS
AND
Trip Temperature
Alarm Temperature
RUN
temperature > Trip Pickup
RUN
temperature > Alarm Pickup
Block
Alarm
OR
None
T –40°C
£
DCMA OUTPUT H1
SOURCE: Off
DCMA OUTPUT H1
RANGE: –1 to 1 mA
SETTINGS
Trip Pickup Delay
SETTINGS
Trip Reset Delay
Application
Trip Voting
Alarm Pickup Delay
T
PKP
Voting logic
T
DPO
T
PKP
From other remote
0
RTDs for voting
Range: Off, any analog actual value parameter
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
To other remote RTDs
for voting
FLEXLOGIC OPERAND
REMOTE RTD 1 TRIP OP
FLEXLOGIC OPERANDS
RRTD 1 ALARM OP
RRTD 1 TRIP PKP
RRTD 1 TRIP DPO
RRTD 1 ALARM PKP
RRTD 1 ALARM DPO
RRTD 1 OPEN
RRTD 1 SHORTED
833026A1.CDR