CHAPTER 5: SETTINGS
GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.
GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
GGIO2 CF SPCSO 1 ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control Virtual Input 1. "sbo" here is select-before-
operate.
GGIO2 CF SPCSO 2 ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
Selects the control model for Virtual Input 2, and so on.
GGIO4
GGIO4 is a UR feature that allows any of up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information
model data attribute.
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-28: GGIO2 panel
PRODUCT SETUP
5
5-71