STATUS

6.2.9 RxGOOSE status

ACTUAL VALUES  STATUS  RxGOOSE STATUS
 RxGOOSE STATUS
The M60 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.

6.2.10 RxGOOSE statistics

ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(16)
 RxGOOSE 1
The M60 is provided with optional IEC 61850 capability. This feature is specified as a software option at
6
the time of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.

6.2.11 Digital counters

ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS
 Counter 1
6-6
All RxGOOSE Online:
Yes
RxGOOSE 1:
Off
RxGOOSE 16:
Off
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
RxGOOSE 1
stNum:
RxGOOSE 1
sqNum:
Counter 1
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
0
Range: Yes, No
Range: On, Off
Range: On, Off
0
0
ACCUM:
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL