CHAPTER 6: ACTUAL VALUES
6.3.2 Stator differential
ACTUAL VALUES METERING STATOR DIFFERENTIAL STATOR DIFFERENTIAL
STATOR
DIFFERENTIAL
The phasors of differential and restraint currents are displayed in primary amperes.
6.3.3 Motor
ACTUAL VALUES METERING MOTOR
MOTOR
There are three metered values available for the motor.
— This value represents the measured three phase average RMS current from the line source divided by the
MOTOR LOAD
Full Load Amps setting, in per unit.
— This value is the amount of unbalance in the motor currents. An explanation of the calculation of this
MOTOR UNBALANCE
value is presented for the AMP Unbalance element.
— Unbalance Bias Motor Load shows the equivalent motor heating current caused by the
U/B BIASED MOTOR LOAD
unbalance k factor.
6.3.4 Sources
6.3.4.1 Menu
ACTUAL VALUES METERING SOURCE SRC 1
SOURCE SRC 1
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
STATOR DIFF OPERATE
Iad: 0.00 A
STATOR DIFF RESTRAIN
Iar: 0.00 A
STATOR DIFF OPERATE
Ibd: 0.00 A
STATOR DIFF RESTRAIN
Iar: 0.00 A
STATOR DIFF OPERATE
Icd: 0.00 A
STATOR DIFF RESTRAIN
Icr: 0.00 A
MOTOR LOAD:
0.00 x FLA
CURRENT UNBALANCE:
0 %
U/B BIASED MOTOR
LOAD: 0.00 x FLA
PHASE CURRENT
SRC 1
GROUND CURRENT
SRC 1
PHASE VOLTAGE
SRC 1
AUXILIARY VOLTAGE
SRC 1
See below
See page 6-16
See page 6-17
See page 6-17
METERING
6
6-15