SUN2000-(30KTL-A, 33KTL, 40KTL)
User Manual
Table 5-2 DC terminal selection requirements
Number of Inputs
1
2
3
4
5
6
Table 5-3 Recommended DC input cable specifications
Cable Type
Common PV cables in
the industry (model:
PV1-F)
Issue 04 (2016-06-20)
Figure 5-15
shows the DC terminals at the bottom of the SUN2000.
the requirements for DC terminal selection.
Figure 5-15 DC terminals
SUN2000
Connected to any one route
Connected to routes 1 and 3
Connected to routes 1, 3, and 5
Connected to routes 1, 2, 3, and 5
Connected to routes 1, 2, 3, 4, and 5
Connected to routes 1, 2, 3, 4, 5, and 6
DC input cable specifications
Table 5-3
lists the recommended DC input cable specifications.
Cross-sectional Area (mm
Range
4.0–6.0 (or 12–10
AWG)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Table 5-2
)
Cable Outer
2
Diameter (mm)
Recommended
Value
4.0 (or 12 AWG)
4.5–7.8