Bmk 1500/2000 Combustion Cal Menus; Bmk 2500/3000 Combustion Cal Menus - Aerco Benchmark BMK 750 User Manual

Benchmark series natural gas fired, modulating and condensing boilers
Hide thumbs Also See for Benchmark BMK 750:
Table of Contents

Advertisement

Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
SECTION 2: OPERATION

2.8.2 BMK 1500/2000 COMBUSTION CAL Menus

TABLE 2-7a: COMBUSTION CAL Menu: BMK 1500/2000
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 18%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level

2.8.3 BMK 2500/3000 COMBUSTION CAL Menus

TABLE 2-8a: COMBUSTION CAL Menu: BMK 2500/3000
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 14%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
Page 22 of 146
11/29/2017
MINIMUM
MAXIMUM
0.25
0.25
0.25
0.25
0.25
0.25
0%
0
10.00 V
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0%
100%
0
10.00 V
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
DEFAULTS
BMK 1500
1.80
10.00
10.00
2.30
10.00
2.50
10.00
2.90
10.00
3.80
10.00
7.90
100%
Displays current value
2.00 V
Displays current value
DEFAULTS
BMK 2500
2.20
4.10
4.80
5.30
6.80
8.50
Variable
Displays current value
2.00 V
Displays current value
BMK 2000
1.40
3.80
4.30
5.40
6.40
9.50
Variable
2.00 V
BMK 3000
2.80
4.60
5.00
5.50
6.90
9.10
2.00 V
OMM-0128_0C
GF-206-K