2.6 CONFIGURATION Menu

The Configuration menu permits adjustment of the Internal Setpoint (Setpt) temperature
regardless of whether the valid password has been entered. Setpt is required for operation in
the CONSTANT SETPOINT mode. The remaining options in this menu require the valid
password to be entered, prior to changing existing entries. This menu contains a number of
other configuration settings which may or may not be displayed, depending on the current
operating mode setting.
A full description of each item appears in Appendix A-3.
NOTE:
The Configuration menu settings are Factory-Set in accordance with the requirements
specified for each individual order. Under normal operating conditions, no changes will be
required.
TABLE 2-4: CONFIGURATION Menu
MENU ITEM DISPLAY
Internal Setpt
1
2
Unit Type
Unit Size
3
(Only displays sizes
available for the unit)
4
Fuel Type
5
Boiler Mode
Remote Signal
(If Mode = Remote
6
Setpoint, Direct Drive
or Combination)
7
Outdoor Sensor
* Bldg Ref Temp
8
(If Mode = Outdoor
Reset)
* Reset Ratio
9
(If Mode = Outdoor
Reset)
* System Start Tmp
10
(If Outdoor Sensor =
Enabled)
Setpt Lo Limit
11
OMM-0128_0C
GF-206-K
AVAILABLE CHOICES OR LIMITS
Minimum
40°F (4.4°C)
BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual
750 MBH (220 kW), 1000 MBH (293
kW), 1500 MBH (439.6 kW), 2000
MBH (586.1 kW), 2500 MBH (732.6
kW), 3000 MBH (879.2 kW)
Natural Gas or Propane
Constant Setpoint, Remote Setpoint,
Direct Drive, Combination,
Outdoor Reset
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS), Network
Enabled or Disabled
40°F
(4.4°C)
0.1
30°F
(-1.1°C)
40°F (4.4°C)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Maximum
240°F (115.6°C)
750 MBH (220 kW),
standard models
Constant Setpoint
230°F
(110°C)
9.9
100°F
(37.8°C)
Setpt Hi Limit
DEFAULT
130°F (54.4°
C)
BMK Boiler LN
Natural Gas in
4 – 20 mA,
1-5V
Disabled
70°F
(21.1°C)
1.2
60°F
(15.6°C)
60°F (15.6°C)