Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
APPENDIX A: BOILER MENU DESCRIPTIONS
TABLE A-3: CONFIGURATION Menu Item Descriptions
MENU OPTIONS
25
Deadband High
26
Deadband Low
27
IGST Version
28
IGN Time Setting
29
Slow Shutdown
30
Slow Sht Duration
31
Slow Sht Threshold
32
O2 Warnings
33
O2 Trim ID
34
Fixed ID
35
O2 Trim Key
36
O2 Trim Menu
37
BST Menu
Page 76 of 146
11/29/2017
Deadband High and Deadband Low settings create an "Outlet
Temperature" Zone in which no Valve Position corrections will
be attempted.
The Deadband ZONE is defined as operating with an Outlet
Temperature between Active Setpoint + Deadband High and
Active Setpoint – Deadband Low.
When the Outlet Temperature reaches Active Setpoint and
remains there for a period of 15 seconds, the unit will go into a
DEADBAND MODE at which point no Valve Position
corrections will be attempted while the Outlet Temperature
remains anywhere within the Deadband ZONE. When the unit
is in the DEADBAND MODE, the °F or °C LED will flash on and
off. When the Outlet Temperature drifts out of the Deadband
ZONE, the DEADBAND MODE will be terminated and the PID
LOOP will again attempt Valve Position corrections.
Setting range is 0°F (0°C) to 25°F (13.75°C). Default is 5°F
(2.75°C) for both Deadband High and Deadband Low).
Displays the version of the IGST Board installed.
Displays the MAX Ignition time of 4 Seconds or 7 Seconds as
set in the Safety String Harness.
Set the Slow Shutdown feature to Enabled or Disabled.
If Slow Shutdown = Enabled, sets the time a boiler will
continue to run at the Stop Level after running above the Slow
Sht Threshold level, up to 9,999 seconds.
Sets the Fire Rate above which a boiler will trigger the Slow
Shutdown feature.
Enables or disables AERtrim warning messages.
Displays 4 digit AERtrim ID number. Pre-populated on all units.
Changes each time the unit is powered up.
Displays the unit's fixed 4 digit ID number. Pre-populated on all
units. Does not change.
Displays the value of the AERtrim 4 digit license key. Pre-
populated on all units.
When set to Enabled, the AERtrim menu options appears.
When set to Enabled, the BST menu options appears.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
DESCRIPTION
OMM-0128_0C
GF-206-K