Automatic Error Reset - REXROTH EFC 3610 Series Operating Instructions Manual

Frequency converter efc x610 series
Hide thumbs Also See for EFC 3610 Series:
Table of Contents

Advertisement

EFC x610 Series

13.5.2 Automatic Error Reset

Automatic error reset function is used to ensure continuous running without hu-
man intervention in the case of occasional errors, such as overcurrent or over-
voltage at start or in the run mode. This function can be activated by setting
[E9.00] ≠ 0.
When an error occurs, the frequency converter stops the output and the related
error code is displayed at the same time. The system remains in idle mode for
delay time [E9.01]. Then the error will automatically be reset and a run com-
mand will be generated to restart the frequency converter. This sequence will be
performed [E9.00] times. If the error still exists, the frequency converter re-
mains in idle mode and no longer performs automatic restart attempts. In this
case, a manual error reset is required to resume the operation.
Automatic error reset is valid for the following errors: OC-1, OC-2, OC-3, OE-1,
OE-2, OE-3, OE-4, OL -1, OL -2, UE-1, E-St, OH and UH.
Code
E9.00 Automatic error reset attempts
E9.01 Automatic error reset interval
DOK-RCON03-EFC-X610***-IT03-EN-P
Name
0...3 (0: Inactive)
2...60 s
Setting range
Default
Bosch Rexroth AG
Diagnosis
Min.
Attri.
0
Stop
10
1
Stop
227/337

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EFC 3610 Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Efc 5610 series

Table of Contents

Save PDF