Page 6
EFC3600 Quick Set up 1) Running from Panel Potentiometer & Buttons § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings • These parameters below are automatically set after b0.05=1 § b1.00 = 0 Frequency set point via potentiometer § ...
Page 7
EFC3600 Quick Set up 2) Running from External I/O Terminal, Frequency Set by Potentiometer § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 0 Frequency set point via potentiometer § b1.02 = 1 Inputting commands via external I/O terminals § ...
Page 8
EFC3600 Quick Set up 3) Running from External I/O Terminal + Jogging, Frequency Set by Potentiometer § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 0 Frequency set point via potentiometer § ...
Page 10
EFC3600 Quick Set up 5) Running with Panel UP/Down Arrows § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 1 Frequency set point via panel Arrows UP/DOWN § b1.02 = 0 Inputting commands via Panel § ...
Page 11
EFC3600 Quick Set up 6) Running External I/O with UP / DOWN / ZERO Inputs § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 4 Frequency set point via external UP/DOWN § ...
Page 12
EFC3600 Quick Set up 7) Running with an Analog Input Voltage § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 2 Frequency set point given via analog input voltage § b1.02 = 1 Inputting commands via External Input § ...
Page 13
EFC3600 Quick Set up 8) Running with Analog Input Voltage switching to 2 Frequency Source &/or Run Source § b0.05 = 1 Load standard parameters § b0.02 = 2 Access all authority settings § b1.00 = 2 Frequency set point given via analog input voltage § ...
Page 14
EFC3600 Quick Set up 9) Simple PLC b0.05 = 1 Load standard parameters § § b0.02 = 2 Access all authority settings § b1.00 = 6 Frequency set point given via MultiSpeed § E2.30 = 1 Simple PLC Active, one cycle then stops § ...