6. FIRST POWER-ON

Before the first power-on, please make sure that all electrical connections are
made properly. Pay special attention to the motor and encoder connections.
See Controller Installation section of this manual for further details.
Having made sure that all electrical connections to the controller are made properly,
position the elevator's car such that the car's door latches on to the shaft's door. Please check
that all mechanical parts of the transmission (guides, rollers, bearings) are in good condition.
This is necessary for proper execution of the calibration procedure.
Before power up the controller slide the door into halh-open position. After power up, the
controller will display the welcome screen, containing the software version number, and
„Initialisation" message. Immediately after controller unpacking its parameters are set by
default settings, which can be restored whenever using „Restore" option in „Default set."
menu.
To prepare
[ESC/MENU] button for 3 seconds. Once in the menu, enter all parameters characterising the
door, and its drive. See the Controller programming section at page 15 for details.
CAUTION! Entering wrong parameters (i.e. not corresponding to actual door
and drive characteristics) may cause malfunction of the door controlled by
SDK-500
The controller uses the entered value of the door's mass and controls the
speed such as to ensure that the door never exceeds the maximum allowed
kinetic energy limit.
When all parameters are set, please perform the „Installation" procedure (see page
19). The door should be driven slowly to fully closed position and then to fully open position.
If start of „Installation" procedure causes door opening it is important to stop
procedure immediately by pressing [ESC/MENU] button. Next switch off the
controller power supply and swap motor power supply lines – J1.1 and J1.2
connectors (see figure 6.1 at page 29). After changing motor power supply
connection „Installation" procedure must be start again.
During this movement terminal positions of the door will be identified and stored in the
controller's non-volatile memory. Then the door will be closed again. Finally, door will open and
close three times with programmed speeds and entered values of the door parameters. During
User's manual for
SDK-500 for working
and/or may pose significant danger to persons using the door.
Fig. 6.1. Motor supply connector
elevator door controller
enter the menu of the controller by holding the
J1
1
2 3
Motor
SDK-500
29