Line distance protection REL650 2.2
Product version: 2.2.1
Table 125. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
× +
t
B k tDef
(
)
ç
÷
P
ç
-
÷
I
1
è
ø
EQUATION1249-SMALL V2 EN-US
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN-US
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
Table 126. IEC Inverse time characteristics for Voltage restrained time overcurrent protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1251-SMALL V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
ABB
GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v1
Range or value
0.10 ≤ k ≤ 3.00
A=28.2, B=0.1217, P=2.0 , tr=29.1
A=19.61, B=0.491, P=2.0 , tr=21.6
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02, tr=4.85
A=64.07, B=0.250, P=2.0, tr=30
A=28.55, B=0.712, P=2.0, tr=13.46
A=0.086, B=0.185, P=0.02, tr=4.6
Range or value
0.10 ≤ k ≤ 3.00
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
1MRK 506 384-BEN A
Accuracy
ANSI/IEEE C37.112 ,
± 5.0% or ±40 ms
whichever is greater
Accuracy
IEC 60255-151, ±5.0%
or ±40 ms whichever is
greater
79