Line distance protection REL650 2.2
Product version: 2.2.1
Bay control QCBAY
The Bay control (QCBAY) function is used together with Local
remote and local remote control functions to handle the
selection of the operator place per bay. QCBAY also provides
blocking functions that can be distributed to different
apparatuses within the bay.
Proxy for signals from switching device via GOOSE
XLNPROXY
The proxy for signals from switching device via GOOSE
(XLNPROXY) gives an internal representation of the position
status and control response for a switch modelled in a
breaker IED. This representation is identical to that of an
SXCBR function.
GOOSE function block to receive a switching device
GOOSEXLNRCV
The GOOSE XLN Receive component is used to collect
information from another device's XCBR/XSWI logical node
sent over process bus via GOOSE. The GOOSE XLN Receive
component includes 12 different outputs (and their respective
channel valid bits) with defined names to ease the 61850
mapping of the GOOSE signals in the configuration process.
Local remote LOCREM/Local remote control LOCREMCTRL
The signals from the local HMI or from an external local/
remote switch are connected via the function blocks
LOCREM and LOCREMCTRL to the Bay control QCBAY
function block. The parameter
LOCREM is set to choose if the switch signals are coming
from the local HMI or from an external hardware switch
connected via binary inputs.
Logic rotating switch for function selection and LHMI
presentation SLGAPC
The logic rotating switch for function selection and LHMI
presentation (SLGAPC) (or the selector switch function block)
is used to get an enhanced selector switch functionality
compared to the one provided by a hardware selector switch.
Hardware selector switches are used extensively by utilities,
in order to have different functions operating on pre-set
values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended
purchase portfolio. The selector switch function eliminates all
these problems.
Selector mini switch VSGAPC
The Selector mini switch (VSGAPC) function block is a
multipurpose function used for a variety of applications, as a
general purpose switch.
VSGAPC can be controlled from the menu, from a symbol on
the single line diagram (SLD) on the local HMI or from Binary
inputs
Generic communication function for Double Point indication
DPGAPC
20
M13447-3 v8
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1
M17086-3 v8
ControlMode in function block
SEMOD114908-4 v10
SEMOD158756-5 v9
Generic communication function for Double Point indication
(DPGAPC) function block is used to send double point
position indications to other systems, equipment or functions
in the substation through IEC 61850-8-1 or other
communication protocols. It is especially intended to be used
in the interlocking station-wide logics.
Single point generic control 8 signals SPC8GAPC
The Single point generic control 8 signals (SPC8GAPC)
function block is a collection of 8 single point commands that
can be used for direct commands for example reset of LEDs
or putting IED in "ChangeLock" state from remote. In this
way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the
result of the commands is supposed to be achieved by other
means, such as binary inputs and SPGAPC function blocks.
The commands can be pulsed or steady with a settable pulse
time.
Automation bits, command function for DNP3.0 AUTOBITS
Automation bits function for DNP3 (AUTOBITS) is used within
PCM600 to get into the configuration of the commands
coming through the DNP3 protocol. The AUTOBITS function
plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).
Single command, 16 signals
The IEDs can receive commands either from a substation
automation system or from the local HMI. The command
function block has outputs that can be used, for example, to
control high voltage apparatuses or for other user defined
functionality.
9. Scheme communication
Scheme communication logic with delta based blocking
scheme signal transmit ZCPSCH
To achieve instantaneous fault clearance for all line faults,
scheme communication logic is provided. All types of
communication schemes for permissive underreaching,
permissive overreaching, blocking, delta based blocking,
unblocking and intertrip are available.
The built-in communication module (LDCM) can be used for
scheme communication signaling when included.
Current reversal and weak-end infeed logic for distance
protection ZCRWPSCH
The ZCRWPSCH function provides the current reversal and
weak end infeed logic functions that supplement the standard
scheme communication logic. It is not suitable for standalone
use as it requires inputs from the distance protection
functions and the scheme communications function included
within the terminal.
On detection of a current reversal, the current reversal logic
provides an output to block the sending of the teleprotection
1MRK 506 384-BEN A
SEMOD55850-5 v7
SEMOD176462-4 v10
SEMOD158591-5 v8
M12446-6 v5
M13860-3 v10
M13896-3 v15