ABB REL650 Product Manual page 68

Relion 650 series, line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 2.2
Product version: 2.2.1
Table 90. Indications
Function
Buffer capacity
Table 91. Event recorder
Function
Buffer capacity
Resolution
Accuracy
Table 92. Trip value recorder
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of disturbance reports
Table 93. Disturbance recorder
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
Table 94. Event counter with limit supervision L4UFCNT
Function
Counter value
Max. count up speed
Table 95. Running hour-meter TEILGAPC
Function
Time limit for alarm supervision, tAlarm
Time limit for warning supervision, tWarning
Time limit for overflow supervision
68
Maximum number of indications presented for single disturbance
Maximum number of recorded disturbances
Maximum number of events in disturbance report
Maximum number of disturbance reports
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Range or value
0-65535
30 pulses/s (50% duty cycle)
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
(0 - 99999.9) hours
(0 - 99999.9) hours
Fixed to 99999.9 hours
M13765-1 v5
M12702-1 v4
M13747-1 v5
M12384-1 v7
Value
40
352
100
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Accuracy
-
-
Range or value
1MRK 506 384-BEN A
Value
352
100
Value
150
100
1 ms
Depending on time
synchronizing
Accuracy
±0.1% of set value
±0.1% of set value
±0.1%
Value
30
100
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650 2.2

Table of Contents