ABB REL650 Product Manual page 54

Relion 650 series, line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 2.2
Product version: 2.2.1
Table 42. Rate-of-change of frequency protection SAPFRC
Function
Operate value, start function
Operate value, restore enable frequency
Definite restore time delay
Definite time delay for frequency gradient trip
Definite reset time delay
54
M14976-1 v9
Range or value
(-10.00-10.00) Hz/s
(45.00-65.00) Hz
(0.000-60.000) s
(0.200-60.000) s
(0.000-60.000) s
1MRK 506 384-BEN A
Accuracy
±10.0 mHz/s
±2.0 mHz
±0.2% or ±100 ms whichever is
greater
±0.2% or ±120 ms whichever is
greater
±0.2% or ±250 ms whichever is
greater
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650 2.2

Table of Contents