ABB REL650 Product Manual page 17

Relion 650 series, line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 2.2
Product version: 2.2.1
EF4PTOC can be set to be directional or non-directional
independently for each step.
IDir, UPol and IPol can be independently selected to be either
zero sequence or negative sequence.
A second harmonic blocking can be set individually for each
step.
Directional operation can be combined together with the
corresponding communication logic in permissive or blocking
teleprotection scheme. The current reversal and weak-end
infeed functionality are available as well.
The residual current can be calculated by summing the three-
phase currents or taking the input from the neutral CT.
Four step directional negative phase sequence overcurrent
protection NS4PTOC
Four step directional negative phase sequence overcurrent
protection (NS4PTOC) has an inverse or definite time delay
independent for each step separately.
All IEC and ANSI time delayed characteristics are available
together with an optional user defined characteristic.
The directional function is voltage polarized.
NS4PTOC can be set directional or non-directional
independently for each of the steps.
NS4PTOC can be used as main protection for unsymmetrical
fault; phase-phase short circuits, phase-phase-earth short
circuits and single phase earth faults.
NS4PTOC can also be used to provide a system backup for
example, in the case of the primary protection being out of
service due to communication or voltage transformer circuit
failure.
Directional operation can be combined together with
corresponding communication logic in permissive or blocking
teleprotection scheme. The same logic as for directional zero
sequence current can be used. Current reversal and weak-
end infeed functionality are available.
Sensitive directional residual overcurrent and power
protection SDEPSDE
In isolated networks or in networks with high impedance
earthing, the earth fault current is significantly smaller than
the short circuit currents. In addition to this, the magnitude of
the fault current is almost independent on the fault location in
the network. The protection can be selected to use either the
residual current or residual power component 3U0·3I0·cos j,
for operating quantity with maintained short circuit capacity.
There is also available one nondirectional 3I0 step and one
3U0 overvoltage tripping step.
ABB
GUID-485E9D36-0032-4559-9204-101539A32F47 v6
SEMOD171438-5 v6
No specific sensitive current input is needed. Sensitive
directional residual overcurrent and power protection
(SDEPSDE) can be set as low 0.25% of IBase.
Thermal overload protection, one time constant LCPTTR/
LFPTTR
The increasing utilization of the power system closer to the
thermal limits has generated a need of a thermal overload
protection for power lines.
A thermal overload will often not be detected by other
protection functions and the introduction of the thermal
overload protection can allow the protected circuit to operate
closer to the thermal limits.
The three-phase current measuring protection has an I
characteristic with settable time constant and a thermal
memory. The temperature is displayed in either Celsius or
Fahrenheit, depending on whether the function used is
Thermal overload protection (LCPTTR) (Celsius) or (LFPTTR)
(Fahrenheit).
An alarm level gives early warning to allow operators to take
action well before the line is tripped.
Estimated time to trip before operation, and estimated time to
reclose after operation are presented.
Breaker failure protection CCRBRF
Breaker failure protection (CCRBRF) ensures a fast backup
tripping of the surrounding breakers in case the own breaker
fails to open. CCRBRF can be current-based, contact-based
or an adaptive combination of these two conditions.
A current check with extremely short reset time is used as
check criterion to achieve high security against unwanted
operation.
Contact check criteria can be used where the fault current
through the breaker is small.
CCRBRF can be single- or three-phase initiated to allow use
with single phase tripping applications. For the three-phase
version of CCRBRF the current criteria can be set to operate
only if two out of four for example, two phases or one phase
plus the residual current start. This gives a higher security to
the back-up trip command.
CCRBRF function can be programmed to give a single- or
three-phase re-trip of its own breaker to avoid unnecessary
tripping of surrounding breakers at an incorrect initiation due
to mistakes during testing.
Pole discordance protection CCPDSC
An open phase can cause negative and zero sequence
currents which cause thermal stress on rotating machines
and can cause unwanted operation of zero sequence or
negative sequence current functions.
1MRK 506 384-BEN A
M12020-4 v14
2
t
M11550-6 v17
M13269-3 v15
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650 2.2

Table of Contents