Supported Information Types; Function Commands User Defined For Iec 60870-5-103; I103Usrcmd; Functionality - ABB IEC 60870-5-103 Communication Protocol Manual

Relion 670 series
Hide thumbs Also See for IEC 60870-5-103:
Table of Contents

Advertisement

1MRK 511 394-UEN A
4.2.2.5
4.2.3
4.2.3.1
4.2.3.2
4.2.3.3
670 series 2.2 IEC
Communication protocol manual
IEC 60870-5-103 vendor specific implementation

Supported information types

Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 35:
I103IEDCMD supported indications
INF
Description
19
LED Reset
23
Activate setting group 1
24
Activate setting group 2
25
Activate setting group 3
26
Activate setting group 4

Function commands user defined for IEC 60870-5-103

I103USRCMD

Functionality

I103USRCMD is a command block in control direction with user defined output
signals. These function blocks include the FunctionType parameter for each block
in the private range, and the Information number parameter for each output signal.

Function block

I103USRCMD
BLOCK
^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8
IEC10000284-1-en.vsd
IEC10000284 V1 EN-US
Figure 15:
I103USRCMD function block

Signals

Table 36:
I103USRCMD Input signals
Name
Type
BLOCK
BOOLEAN
Default
Description
0
Block of commands
Section 4
M11874-29 v6
GUID-2989EAC8-20BE-46EE-93FE-C70188D0BC89 v1
GUID-5EBEAED5-ABD9-4257-B879-DF7FD9F7805A v1
PID-3790-INPUTSIGNALS v5