ABB IEC 60870-5-103 Communication Protocol Manual page 27

Relion 670 series
Hide thumbs Also See for IEC 60870-5-103:
Table of Contents

Advertisement

1MRK 511 394-UEN A
Table 3:
OPTICAL103 Non group settings (basic)
Name
Values (Range)
SlaveAddress
BaudRate
RevPolarity
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
CmdMode
RepIntermediatePos
670 series 2.2 IEC
Communication protocol manual
Unit
1 - 254
-
9600 Bd
-
19200 Bd
Off
-
On
1.0 - 1800.0
s
UTC
-
Local without DST
Local with DST
IEDTime
-
LinMastTime
IEDTimeSkew
Off
-
5ms
10ms
20ms
40ms
SeqOfEvent
-
HiPriSpont
MultiCmd
-
SingleCmd
Off
-
On
IEC 60870-5-103 communication engineering
Step
Default
1
1
-
9600 Bd
-
On
0.1
5.0
-
UTC
-
IEDTime
-
5ms
-
SeqOfEvent
-
SingleCmd
-
On
Section 3
Description
Slave address
Baudrate on serial line
Invert polarity
Cyclic reporting time of measurments
Master time domain
Time synchronization mode
Evaluate time accuracy for invalid time
Event reporting mode
Command handling mode
Report intermediate position
PID-6610-SETTINGS v5
21

Advertisement

Table of Contents
loading