Signals; Settings; Supported Information Types - ABB IEC 60870-5-103 Communication Protocol Manual

Relion 670 series
Hide thumbs Also See for IEC 60870-5-103:
Table of Contents

Advertisement

1MRK 511 394-UEN A
4.2.1.3
4.2.1.4
Table 30:
I103CMD Non group settings (basic)
Name
Values (Range)
FunctionType
4.2.1.5
670 series 2.2 IEC
Communication protocol manual
IEC 60870-5-103 vendor specific implementation

Signals

Table 28:
I103CMD Input signals
Name
BLOCK
Table 29:
I103CMD Output signals
Name
16-AR
17-DIFF
18-PROT

Settings

Unit
1 - 255
-

Supported information types

Function commands in control direction, pre-defined I103CMD
Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 31:
Pre-defined I103CMD supported indications
INF
Description
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
Type
Default
Description
BOOLEAN
0
Block of commands
Type
Description
BOOLEAN
Information number 16, off/on of autorecloser
BOOLEAN
Information number 17, block of differential
protection
BOOLEAN
Information number 18, block of protection
Step
Default
1
1
Section 4
PID-3969-INPUTSIGNALS v5
PID-3969-OUTPUTSIGNALS v5
Description
Function type (1-255)
PID-3969-SETTINGS v5
M11874-53 v6
41

Advertisement

Table of Contents
loading

Table of Contents