Section 4
IEC 60870-5-103 vendor specific implementation
4.2.2
4.2.2.1
4.2.2.2
4.2.2.3
4.2.2.4
Table 34:
I103IEDCMD Non group settings (basic)
Name
FunctionType
42
IED commands for IEC 60870-5-103 I103IEDCMD
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
Function block
I103IEDCMD
BLOCK
19-LEDRS
IEC10000283-1-en.vsd
IEC10000283 V1 EN-US
Figure 14:
I103IEDCMD function block
Signals
Table 32:
I103IEDCMD Input signals
Name
BLOCK
Table 33:
I103IEDCMD Output signals
Name
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
Settings
Values (Range)
Unit
1 - 255
-
23-GRP1
24-GRP2
25-GRP3
26-GRP4
Type
Default
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
1
255
1MRK 511 394-UEN A
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
Description
Block of commands
Description
Information number 19, reset LEDs
Information number 23, activate setting group 1
Information number 24, activate setting group 2
Information number 25, activate setting group 3
Information number 26, activate setting group 4
Description
Function type (1-255)
Communication protocol manual
PID-3788-INPUTSIGNALS v5
PID-3788-OUTPUTSIGNALS v5
PID-3788-SETTINGS v5
670 series 2.2 IEC