Status For User Defined Signals For Iec 60870-5-103; I103Usrdef; Functionality; Function Block - ABB IEC 60870-5-103 Communication Protocol Manual

Relion 670 series
Hide thumbs Also See for IEC 60870-5-103:
Table of Contents

Advertisement

1MRK 511 394-UEN A
4.1.8
4.1.8.1
4.1.8.2
670 series 2.2 IEC
Communication protocol manual
IEC 60870-5-103 vendor specific implementation
Table 24:
I103SUPERV supported functions
INF
Description
32
Measurand supervision I
33
Measurand supervision U
37
I>>back-up operation
38
VT fuse failure
46
Group warning
47
Group alarm

Status for user defined signals for IEC 60870-5-103

I103USRDEF

Functionality

I103USRDEF is a function block with user defined input signals in monitor
direction. Each instance is associated with a Function Type (FUN) and each input
signal with an Information Number (INF). Additionally, all input signals may be
defined to use relative time and how to respond to a GI request.
The user is responsible for assigning a proper FUN value and proper INF values to
all connected inputs. See Settings for details.

Function block

I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START
IEC10000294-3-en.vsdx
IEC10000294 V3 EN-US
Figure 12:
I103USRDEF function block
TYP
GI
COT
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3
GUID-B8312E77-514D-4117-BB31-B9907755580C v1
Section 4
37