Section 4
IEC 60870-5-103 vendor specific implementation
4.1.8.5
4.2
4.2.1
4.2.1.1
4.2.1.2
40

Supported information types

Function status indications in monitor direction, user-defined,
I103USRDEF
Function indication block in monitor direction with user-defined input signals.
Number of instances: 20
Function type is selected with parameter FunctionType.
Information number is required for each input signal.
Table 27:
I103USRDEF Information number default values
INF
Description
Input signal 01
1)
1
2*
Input signal 02
3*
Input signal 03
4*
Input signal 04
5*
Input signal 05
6*
Input signal 06
7*
Input signal 07
8*
Input signal 08
1) * User defined information number

Commands in control direction

Function commands for IEC 60870-5-103 I103CMD

Functionality

I103CMD is a command function block in control direction with pre-defined
output signals. The signals are in steady state, not pulsed, and stored in the IED in
case of restart.

Function block

I103CMD
BLOCK
16-AR
17-DIFF
18-PROT
IEC10000282-1-en.vsd
IEC10000282 V1 EN-US
Figure 13:
I103CMD function block
GI
TYP
COT
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
x/-
1/2
1,7,(9)
Communication protocol manual
1MRK 511 394-UEN A
M11874-137 v7
M11874-27 v1
GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v2
GUID-C0680812-C488-4546-AA65-F590955DBF0C v1
670 series 2.2 IEC