Settings; Supported Information Types; Supervison Status For Iec 60870-5-103 I103Superv; Functionality - ABB IEC 60870-5-103 Communication Protocol Manual

Relion 670 series
Hide thumbs Also See for IEC 60870-5-103:
Table of Contents

Advertisement

1MRK 511 394-UEN A
4.1.6.4
Table 20:
I103IED Non group settings (basic)
Name
Values (Range)
FunctionType
4.1.6.5
4.1.7
4.1.7.1
670 series 2.2 IEC
Communication protocol manual
IEC 60870-5-103 vendor specific implementation
Name
23_GRP1
24_GRP2
25_GRP3
26_GRP4

Settings

Unit
1 - 255
-

Supported information types

Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signals.
Table 21:
I103IED supported functions
INF
Description
19
LED reset
21
TestMode
22
Local Parameter setting
23
Setting group 1 active
24
Setting group 2 active
25
Setting group 3 active
26
Setting group 4 active

Supervison status for IEC 60870-5-103 I103SUPERV

Functionality

I103SUPERV is a function block with defined functions for supervision indications
in monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
Type
Default
Description
BOOLEAN
0
Information number 23, setting group 1 is active
BOOLEAN
0
Information number 24, setting group 2 is active
BOOLEAN
0
Information number 25, setting group 3 is active
BOOLEAN
0
Information number 26, setting group 4 is active
Step
Default
1
1
Section 4
Description
Function type (1-255)
GUID-E7A28D8D-398E-437C-9B58-AE125BC38058 v1
PID-3975-SETTINGS v5
M11874-109 v7
35

Advertisement

Table of Contents
loading

Table of Contents