Section 14
Control
14.4.9
14.4.9.1
14.4.9.2
378

Interlocking for 1 1/2 CB BH

Application
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,
BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter
according to figure 168.
QB1
QA1
QB6
BH_LINE_A
QB9
IEC04000513 V1 EN-US
Figure 168:
Switchyard layout 1 1/2 breaker
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.
For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
Configuration setting
For application without QB9 and QC9, just set the appropriate inputs to open state
and disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
QC1
QC2
QC3
QA1
QB61
QB62
QC1
QC2
QC9
BH_CONN
1MRK 511 401-UEN A
IP14173-1 v3
M13570-3 v6
WA1 (A)
WA2 (B)
QB2
QC1
QA1
QC2
QB6
QC3
BH_LINE_B
QB9
QC9
en04000513.vsd
M13570-7 v4
M13569-4 v4
M13569-6 v5
Bay control REC670 2.2 IEC
Application manual