Signals In Double-Breaker Arrangement - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
14.4.6.3
366
QB2OPTR (QB220OTR)(bay 1/sect.B1)
QB2OPTR (QB220OTR)(bay n/sect.B1)
VPQB2TR (VQB220TR)(bay 1/sect.B1)
VPQB2TR (VQB220TR)(bay n/sect.B1)
EXDU_BB (bay 1/sect.B1)
EXDU_BB (bay n/sect.B1)
IEC04000496 V1 EN-US
Figure 150:
Signals from any bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are
valid:
QB2OPTR (QB220OTR)(bay 1/sect.B2)
QB2OPTR (QB220OTR)(bay n/sect.B2)
DCOPTR (B2/B3)
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)
VPDCTR (B2/B3)
EXDU_BB (bay 1/sect.B2)
EXDU_BB (bay n/sect.B2)
EXDU_DC (B2/B3)
IEC04000497 V1 EN-US
Figure 151:
Signals from any bays in section B2 to a bus-section disconnector

Signals in double-breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbar
disconnector bay no other disconnector connected to the bus-section must be made
by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,
corresponding signals from busbar B are used.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
1MRK 511 401-UEN A
S1DC_OP
&
VPS1_DC
&
EXDU_BB
&
en04000496.vsd
S2DC_OP
&
VPS2_DC
&
EXDU_BB
&
en04000497.vsd
M13542-80 v5
Bay control REC670 2.2 IEC
Application manual